FRONIUS Symo Inverter 10.0-3-M
FRONIUS SYMO 10.0-3-M INVERTER
MAXIMUM FLEXIBILITY FOR TOMORROW'S APPLICATIONS
Fronius Symo 10.0-3-M Inverter. With power classes ranging from 3.0 to 20.0 kW, the Fronius Symo three-phase transformerless inverter is the ideal device for use in installations of any size. Thanks to its SuperFlex Design, the Fronius Symo is optimally suited for curved roofs or roofs of varying construction. Standard Internet connectivity via WLAN or Ethernet and the ability to easily integrate third-party components make the Fronius Symo one of the most "communicative" inverters available on the market. In addition, the meter connector allows for dynamic power management and clear visualization of consumption. INPUT DATA
Number of MPP trackers
2
Max. input current (I dc max )
27,0 / 16,5 A
Max. short-circuit current of the module field
40,5 / 24,8 A
DC input voltage range (U dc min - U dc max )
200 - 1000 V
Start voltage (U dc start )
200 V
Rated input voltage (U dc,r )
600 V
MPP voltage range (U mpp min - U mpp max )
270 - 800 V
Useful MPP voltage range
200 - 800 V
Number of DC connections
3 + 3
Max. photovoltaic generator power (P dc max )
15 kWpeak OUTPUT DATA
AC rated power (P ac,r )
10 kW
Max. output power (P ac max )
10 kVA
AC output current (I ac nom )
14,4 A
Mains connection (U ac,r )
3~ NPE 400/230, 3~ NPE 380/220 V
AC voltage range (U min - U max )
150 - 280 V
Frequency (f r )
50 / 60 Hz
Frequency range (f min - f max )
45 - 65 Hz
Coefficient of non-linear distortion
1,8 %
Power factor (cos φ ac,r )
0 - 1 ind./cap. GENERAL DATA
Dimensions (width)
510 mm
Weight
34,8 kg
Degree of protection
IP 66
Protection class
1
Overvoltage category (DC/AC) 1)
2 / 3
Power consumption at night
< 1 w 1="">
Inverter design concept
Transformerless
Cooling
Adjustable ventilation
Mounting
Indoor and outdoor mounting
Ambient temperature range
-40°C - +60°C
Permissible air humidity
0 - 100 %
Max. altitude above sea level 2)
2.000 m / 3,400 m
DC connection technology
Screw terminals 6x DC+ and 6x DC- 2.5-16 mm²
AC connection technology
5-pin AC screw terminals 2.5-16 mm²
Certifications and standards
ÖVE / ÖNORM E 8001-4-712, DIN V VDE 0126-1-1/A1, VDE AR N 4105, IEC 62109-1/-2, IEC 62116, IEC 61727, AS 3100,
AS 4777-2, AS 4777-3, CER 06-190, G83/2, UNE 206007-1, SI 4777, CEI 0-16, CEI 0-21, NRS 097 EFFICIENCY FACTOR
Max. efficiency factor (photovoltaic installation - mains)
98 %
European efficiency factor (ηEU)
97,4 %
η at 5% P ac,r 3)
87,9 / 92,5 / 89,2 %
η at 10% P ac,r 3)
91,2 / 94,9 / 92,8 %
η at 20% P ac,r 3)
94,6 / 97,1 / 96,1 %
η at 25% P ac,r 3)
95,4 / 97,3 / 96,6 %
η at 30% P ac,r 3)
95,6 / 97,5 / 96,9 %
η at 50% P ac,r 3)
96,3 / 97,9 / 97,4 %
η at 75% P ac,r 3)
96,5 / 98,0 / 97,6 %
η at 100% P ac,r 3)
96,5 / 98,0 / 97,6 %
MPP adjustment efficiency factor
> 99.9 % PROTECTION
DC insulation measurement
Yes
Overload behavior
Offset operating point, power limiter
DC disconnect
Yes CONNECTIONS
WLAN / Ethernet LAN
Fronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6 inputs and 4 digital inputs/outputs
Connection to remote control receiver
USB (type A socket) 4)
Datalogging, inverter update via USB media
2x RS422 (RJ45 socket) 4)
Fronius Solar Net
Signaling output 4)
Energy management (potential-free relay output)
Datalogger and web server
Integrated
External input 4)
S0 counter connection / surge protection monitoring
RS485