Circulation pump Wilo-Stratos MAXO 40/0.5-12 PN6/10
Special offer

Brand
Entity responsible for this product in the EU
WILO-POLSKA SP.Z O.O.More
Address:
JEDNOŚCI 5Postal code: 05-506City: LESZNOWOLACountry: PolenE-mail: wilo.pl@wilo.com
Producer code
4048482699608
Series
Warranty
Manufacturer's Index
2164584
The Wilo-Stratos MAXO Smart Premium pump is a glandless Inline pump with the highest efficiency, equipped with an EC motor and an advanced electronic capacity matching system. The unit is designed for hot water, cold water and water-glycol mixtures, achieving a very low EEI - ≤ 0.17 or ≤ 0.19, respectively, depending on the pump type
The control system offers multiple modes, including
- Wilo-Dynamic Adapt plus: constant, automatic adaptation of power to the system's requirements without the need for setpoints, providing energy savings of up to 20% compared to dp-v control mode
- Constant temperature control (T-const.)
- Differential constant temperature control (dT-const.)
- Multi-Flow Adaptation: optimization of rotary flow by communicating with several pumps
- Constant flow mode (Q-const.)
- Remote point differential pressure control (dp-c) and variable differential pressure control (dp-v) with nominal operating point setting option
- Constant speed (n-const.)
- User-defined PID control
Additional pump functions include
- Heat and cold quantity recording
- Automatic shutdown when zero flow is detected (No-Flow Stop)
- Switching between heating and cooling modes - automatically, externally or manually
- Adjustable flow limitation by Q-Limit function (Qmin and Qmax setting)
- Optimized operation of dual pumps (primary mode and reserve mode) by connecting for dp-c and dp-v
- Saving and restoring settings (up to 3 restore points)
- Failure and warning signaling in text form with help
- Function of automatic venting of the rotor chamber
- Automatic operation in night setback mode
- Non-locking function and full motor protection
- Dry operation detection
The display can read the type of control, setpoint, flow rate, temperature, power consumption, current consumption and active signals (e.g. STOP, No-Flow Stop), among others
The Smart Premium system version includes
- 2 configurable analog inputs (0-10 V, 2-10 V, 0-20 mA, 4-20 mA and standard PT1000) with +24 V DC power supply
- 2 configurable digital inputs (e.g. Ext. Off, Ext. Min, Ext. Max, heating/cooling, manual override, key lock and remote control configuration protection)
- 2 configurable relays for signaling operation and failure messages
- Wilo CIF module slot with interfaces for building automation (optional modules: Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CANopen)
- Wilo Net system for communication between Wilo products (including Multi-Flow Adaptation; integration of dual pumps and Wilo-Smart Gateway)
- Integrated temperature sensors
- Automatic fail-safe mode (preset speed in case of communication failure or erroneous sensor readings)
- Graphic 4.3-inch color display with manual operation module (one button)
- Reading and setting of operation data and preparation of commissioning report via Bluetooth (Wilo-Assistant application)
- Management of dual pump operation integrated (combination of two single pumps into a dual unit, communication via Wilo Net)
- Analog signal break detection capability (using 2-10 V or 4-20 mA signals)
- Possibility of external mounting with protection against climatic factors according to the instructions
- Serial date and time setting
- Thermal insulation covers for heating systems
Scope of delivery includes
- Wilo-Stratos MAXO premium smart pump
- Optimized Wilo-Connector for all sizes
- 2× cable glands M16 x 1.5
- Washers for M12 and M16 flange bolts (for connection of DN 32 and DN 65)
- 2× gaskets for the threaded connection
- Thermal insulation covers
- Compact installation and operating instructions
- Optional accessories (e.g. ClimaForm refrigeration insulation, CIF modules, PT 1000 sensors, immersion sleeve transmitter, differential pressure sensor)
Technical Data
- Energy efficiency index (EEI): ≤ 0.17 or ≤ 0.19
- Pump type: Glandless Inline
- Motor: EC
- Medium: Hot water, cold water or a mixture of water and glycol
- Controls
- Wilo-Dynamic Adapt plus - automatic power adjustment (factory setting)
- Fixed temperature (T-const.)
- Differential constant temperature (dT-const.)
- Multi-Flow Adaptation - optimization of rotating flow by communicating with other pumps
- Constant flow (Q-const.)
- Differential pressure control dp-c (at the remote point) and variable differential pressure dp-v with nominal setting capability
- Constant speed (n-const.)
- User-defined PID control
- Additional functions
- Heat and cold quantity recording
- No-Flow Stop - automatic shutdown at zero flow rate
- Automatic, external and manual switching of heating/cooling modes
- Q-Limit function - flow limitation (Qmin and Qmax)
- Dual pump modes - efficiency optimization (basic and reserve mode)
- Saving and restoring settings (up to 3 points)
- Failure/warning signaling in text form
- Automatic venting of the impeller chamber
- Operation in night setback mode
- Non-locking function and full motor protection
- Dry operation detection
- Inputs and communication
- 2 configurable analog inputs (0-10 V, 2-10 V, 0-20 mA, 4-20 mA, standard PT1000) - +24 V DC power supply
- 2 digital inputs configurable (including Ext. Off, Ext. Min, Ext. Max, heating/cooling, manual override, key lock and remote control configuration protection)
- 2 configurable relays for signaling operation and failure messages
- Wilo CIF module slot with interfaces for building automation (optional: Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet IP, LON, PLR, CANopen)
- Communication via Wilo Net system (including for Multi-Flow Adaptation, dual pumps and Wilo-Smart Gateway)
- Display and control
- Graphic color display 4.3 inches
- One-button manual operation module
- Bluetooth interface for reading, parameter setting and protocol generation (Wilo-Assistant app)
- Protection and safety
- Automatic shutdown at zero flow (No-Flow Stop)
- Protection against overpressure, current overload, low/high voltage, and over-temperature of motor and electronics
- Automatic emergency mode - fixed speed in emergency situations
- External protection: Outdoor mounting with climate protection; thermal insulation covers for heating systems
- Date and time: Set as standard
- Scope of delivery
- Wilo-Stratos MAXO premium smart pump
- Optimized Wilo Connector
- 2× cable glands M16 x 1.5
- Washers for M12 and M16 flange bolts (for connection of DN 32 and DN 65)
- 2× gaskets for the threaded connection
- Thermal insulation covers
- Compact installation and operating instructions
- Optional accessories (e.g. ClimaForm refrigeration insulation, CIF modules, PT 1000 sensors, transmitter, differential pressure sensor)
Ask a question